Accurate observation coding on an Electrical Installation Condition Report (EICR) is critical. Incorrectly assigning a Code C2 where a Code C3 belongs can cost property owners thousands of pounds in unnecessary remedial work, while under-coding a Code C1 hazard leaves occupiers at risk of shock or fire.
In this guide, we analyze the official classification criteria from IET Guidance Note 3 (Section 3) and BS 7671:2018+A4:2026.
The Four EICR Classification Codes
Code C1: Danger Present
Definition: Risk of injury is present. Immediate remedial action is required. The inspector must issue an immediate Notice of Unsafe Situation to the person ordering the report.
Real-world C1 Examples:
- Exposed live 230V terminals accessible without the use of a tool or key.
- Conductive metal enclosure energised due to a dead short.
- Missing enclosure cover exposing live busbars in a accessible consumer unit.
Code C2: Potentially Dangerous
Definition: Urgent remedial action required. While not presenting immediate danger at the time of inspection, a failure mechanism or logical fault could become dangerous under secondary conditions.
Real-world C2 Examples:
- Absence of main protective earthing or main protective bonding to gas/water services.
- Earth fault loop impedance ($Z_s$) exceeding the maximum tabulated limit in BS 7671 where automatic disconnection (ADS) is not guaranteed.
- Absence of 30mA RCD protection for socket-outlets used by ordinary persons where required by Regulation 411.3.3.
- Thermal damage, severe scorching, or melted insulation on terminals.
Code C3: Improvement Recommended
Definition: Non-compliance with BS 7671 that does not present immediate or potential danger, but improvement would enhance safety or bring the installation up to modern standards.
Real-world C3 Examples:
- Absence of circuit identification diagrams or schedule at the consumer unit.
- Wiring colors matching older pre-harmonized BS 7671 standards (e.g. Red/Black) without warning label.
- Non-fire-rated plastic consumer unit in a domestic dwelling (where no damage or overheating exists).
Code FI: Further Investigation Required
Definition: An observation that cannot be fully determined during inspection without further investigation, or where access limitations prevent verifying safety.
Real-world FI Examples:
- Unidentified sub-main cables with unknown protective device rating at source.
- Circuits showing unacceptably low insulation resistance where the cause cannot be pinpointed without invasive tracing.
Impact on Overall EICR Outcome
| Observations Present | Overall Assessment Outcome |
|---|---|
| Any Code C1 present | UNSATISFACTORY |
| Any Code C2 present | UNSATISFACTORY |
| Any Code FI present | UNSATISFACTORY |
| Only Code C3 or no defects | SATISFACTORY |
Practice Fault Coding Online
Test your decision-making with our interactive EICR Fault Coding Trainer and check out our recommended inspection books and equipment to refine your skills for the City & Guilds 2391-52 exam.
Ready to Master City & Guilds 2391-52?
Practice 445 exam questions, calculate max Zs values, and generate EIC & EICR certificates directly on your phone.
Download 2391 Pro AppRelated Study Guides
BS 7671:2018+A4:2026 Inspection & Testing Updates Explained
Key changes in Amendment 4 (2026) affecting electrical inspection, EIC certificates, EV charging points, and protective conductor testing.
Exam PrepHow to Pass the City & Guilds 2391-52 Exam: The Ultimate 2026 Guide
Master the C&G 2391-52 combined initial verification and periodic inspection exam with our proven study strategy, BS 7671 reference tips, and practical test sequence guide.